Question:
I have closed off my gas furnace and sealed all the cracks with expanding foam, door not on yet, and have four 16×25x1 air filters built in to the wall. When I do put the door on will I need to pump combustion air in or will the filters allow enough flow? Also the vent pipe from the furnace goes outside one of the walls, it seems to get very hot, what is safe to put on the outside of the pipe to seal things off? expanding foam? Thanks
Response:
Why do you have filters in the wall? The furnace does not care if it burns dirty air. I do not think this is a good idea. Starving a furnace of oxygen for combustion creates carbon monoxide. Also if flow is restricted then it is more likely that the exhaust and heat will not go out the vent as they are supposed to. This could possibly result in backflow and fire. Pull out the filters and ensure an uninterupted flow of fresh air to the furnace. You do not want to kill yourself and your family do you? Expanding foam is flammable (I think) and I would not use it to seal a vent pipe. Why are you concerned about sealing the vent pipe in this way? The usual slip or snap connections provide an adequate seal. The exhaust is not under much pressure so you do not need to be so concerned about sealing this. Since you don’t seem to have much knowledge about this, I recommend that you consult a local professional. If you keep going the way you are going you may create a very dangerous situation. — -Jack
– Hide quoted text — Show quoted text – I have closed off my gas furnace and sealed all the cracks with expanding foam, door not on yet, and have four 16×25x1 air filters built in to the wall. When I do put the door on will I need to pump combustion air in or will the filters allow enough flow? Also the vent pipe from the furnace goes outside one of the walls, it seems to get very hot, what is safe to put on the outside of the pipe to seal things off? expanding foam? Thanks
Response:
The only thing I would add is, any time you have an exhaust flue pipe going through any type wood barrier, it should be either double wall air gap pipe or triple wall air gap pipe, depending on the inside temperature of the exhaust. I agree, you need professional advice for what you are trying to do, which I assume is to ward off a dust fire. Tom J
– Hide quoted text — Show quoted text – Why do you have filters in the wall? The furnace does not care if it burns dirty air. I do not think this is a good idea. Starving a furnace of oxygen for combustion creates carbon monoxide. Also if flow is restricted then it is more likely that the exhaust and heat will not go out the vent as they are supposed to. This could possibly result in backflow and fire. Pull out the filters and ensure an uninterupted flow of fresh air to the furnace. You do not want to kill yourself and your family do you? Expanding foam is flammable (I think) and I would not use it to seal a vent pipe. Why are you concerned about sealing the vent pipe in this way? The usual slip or snap connections provide an adequate seal. The exhaust is not under much pressure so you do not need to be so concerned about sealing this. Since you don’t seem to have much knowledge about this, I recommend that you consult a local professional. If you keep going the way you are going you may create a very dangerous situation. — -Jack I have closed off my gas furnace and sealed all the cracks with expanding foam, door not on yet, and have four 16×25x1 air filters built in to the wall. When I do put the door on will I need to pump combustion air in or will the filters allow enough flow? Also the vent pipe from the furnace goes outside one of the walls, it seems to get very hot, what is safe to put on the outside of the pipe to seal things off? expanding foam? Thanks
Response:
You might want to check with the local building code people. Whether something will "work" or not isn’t enough. If it "works" but is illegal and your building goes up, your insurance people may be inclined to take a pass on paying off.
– Hide quoted text — Show quoted text – I have closed off my gas furnace and sealed all the cracks with expanding foam, door not on yet, and have four 16×25x1 air filters built in to the wall. When I do put the door on will I need to pump combustion air in or will the filters allow enough flow? Also the vent pipe from the furnace goes outside one of the walls, it seems to get very hot, what is safe to put on the outside of the pipe to seal things off? expanding foam? Thanks
Response:
Chip, you’re scaring me here. I’m sure that your plan is a good one, but before you go any further, you may want to spend $50 for a service call and have a qualified (furnace) tech. come out and "oversee" what you’re trying to do. Between Fire and Carbon Monoxide, furnace modifications are not something you want to take lightly. Good luck and please make that call.. Rob http://www.robswoodworking.com
– Hide quoted text — Show quoted text – I have closed off my gas furnace and sealed all the cracks with expanding foam, door not on yet, and have four 16×25x1 air filters built in to the wall. When I do put the door on will I need to pump combustion air in or will the filters allow enough flow? Also the vent pipe from the furnace goes outside one of the walls, it seems to get very hot, what is safe to put on the outside of the pipe to seal things off? expanding foam? Thanks
Response:
Going to throw in my two pennies here—I totally agree with the other guys–are you trying to seal off the furnace, so shop fumes/dust don;t get spread through the house? I can see the advantage of that, but there are mechanical codes for a reason…to protect your lives and posessions. Call a pro–ask if he will sit down with you to consult on how to do this the right way—it’s money well spent—tell him that you will have him or someone experienced do the work, and he might be willing to give you some up front advice in order to get the business—LISTEN to what he has to say! IN general, the amount of combustion air that has to be available to the furnace AT THE ABSOLUTE MINIMUM! is the amount of airthat gets soncumed in combustion, plus the volume of flue gasses going up(or out) the exhaust flue. THe calculations can get complex depending on different factors, and most HVAC shops of any size have at least one engineer on staff, with the calculating software(costing thousands, sometimes), to figure it out, based on the recent codes. THis isn;t a guess and by golly thing to try at home. To seal the exhaust duct to the chiney/flue, etc., there are special high temperature compounds that get used–if the flue goes into masonary, and is of a high enough temperature, often refractory cement is used to make the seal–other compounds are used on other materials, including the double and triple wall flues. One possibility to ask your HVAC pro about, is if you can get the type of multiple wall flue. that has one passage for INCOMING combustion air, and another pasage for outgoing gasses. THis helps kinda preheat the combustion air a bit, and helps keep the furnace area a bit warmer. Good luck, and, please!! Call a pro in on this!! Don;t take a chance with you, your families lives and possesions!!
– Hide quoted text — Show quoted text – Chip, you’re scaring me here. I’m sure that your plan is a good one, but before you go any further, you may want to spend $50 for a service call and have a qualified (furnace) tech. come out and "oversee" what you’re trying to do. Between Fire and Carbon Monoxide, furnace modifications are not something you want to take lightly. Good luck and please make that call.. Rob http://www.robswoodworking.com I have closed off my gas furnace and sealed all the cracks with expanding foam, door not on yet, and have four 16×25x1 air filters built in to the wall. When I do put the door on will I need to pump combustion air in or will the filters allow enough flow? Also the vent pipe from the furnace goes outside one of the walls, it seems to get very hot, what is safe to put on the outside of the pipe to seal things off? expanding foam? Thanks
Response:
I have closed off my gas furnace and sealed all the cracks with expanding foam, door not on yet, and have four 16×25x1 air filters built in to the wall. When I do put the door on will I need to pump combustion air in or will the filters allow enough flow? Also the vent pipe from the furnace goes outside one of the walls, it seems to get very hot, what is safe to put on the outside of the pipe to seal things off? expanding foam? Thanks
First, you should not be doing what you are doing. The fact that you have done this much without proper knowledge could put your family at risk. This was not smart. Furnaces have vent requirements. Check the owners manual. Some must have 3-4 feet of free space in front or on the sides, others can be located pretty close to a wall. Each brand has its own requriements. As for make up air, it depends on the furnace and the efficiency. Mine is about 10 years old, 80+, and it gets make up air from the house. Choking off that air supply could cause all kinds of problems including failure to vent, which could kill everyone in the house potentially. Yes, there are safety features to prevent this, but I would rather do it right than rely on a feature. If you do not get a good vent, which could happen with a lack of make up air, the fumes stay in the house. At the least, get a carbon monoxide detector near the furnace RIGHT NOW. Some models use a direct vent system where the intake and exhaust come through one pipe. The inside pipe does one while the space around it does the other. In this case make up air is usually not needed.
Response:
I agree with the other’s. The amount of combustion air depends on the furnace, type, and # of BTUs of input. It is really simple for the most part and would follow all the rules for putting a grate in a furnace room door. The best way would be to consult a Pro. I could give you HVAC formulas but there are too many variations. — Young Carpenter "If you’re not confused, You’re not trying hard enough!"
I have closed off my gas furnace and sealed all the cracks with expanding foam, door not on yet, and have four 16×25x1 air filters built in to the wall. When I do put the door on will I need to pump combustion air in or will the filters allow enough flow? Also the vent pipe from the furnace goes outside one of the walls, it seems to get very hot, what is safe to put on the outside of the pipe to seal things off? expanding foam? Thanks
—–= Posted via Newsfeeds.Com, Uncensored Usenet News =—– http://www.newsfeeds.com – The #1 Newsgroup Service in the World! —–== Over 80,000 Newsgroups – 16 Different Servers! =—–
Response:
well, maybe I should have been more clear. I have built 2 walls 10 feet out on each side from the furnace. One of the walls contains 4 25×16x1 furnace filters, so one wall is half filters. The room is by no means closed off to air, Yes I did seal off the other joints except for the door which is not on yet. I have not altered how the furnace vents, I just want to seal around the vent pipe. This mainly to seal out dust, yes I have several dust collectors and filters but dust still gets in. I’ve quite often seen gas furnaces and waters heaters in closed off rooms with no type of incoming air. Let’s all chill out for the moment.
– Hide quoted text — Show quoted text – I have closed off my gas furnace and sealed all the cracks with expanding foam, door not on yet, and have four 16×25x1 air filters built in to the wall. When I do put the door on will I need to pump combustion air in or will the filters allow enough flow? Also the vent pipe from the furnace goes outside one of the walls, it seems to get very hot, what is safe to put on the outside of the pipe to seal things off? expanding foam? Thanks First, you should not be doing what you are doing. The fact that you have done this much without proper knowledge could put your family at risk. This was not smart. Furnaces have vent requirements. Check the owners manual. Some must have 3-4 feet of free space in front or on the sides, others can be located pretty close to a wall. Each brand has its own requriements. As for make up air, it depends on the furnace and the efficiency. Mine is about 10 years old, 80+, and it gets make up air from the house. Choking off that air supply could cause all kinds of problems including failure to vent, which could kill everyone in the house potentially. Yes, there are safety features to prevent this, but I would rather do it right than rely on a feature. If you do not get a good vent, which could happen with a lack of make up air, the fumes stay in the house. At the least, get a carbon monoxide detector near the furnace RIGHT NOW. Some models use a direct vent system where the intake and exhaust come through one pipe. The inside pipe does one while the space around it does the other. In this case make up air is usually not needed.
Response:
. I’ve quite often seen gas furnaces and waters heaters in closed off rooms with no type of incoming air.
I have too, it does not mean it is right though! You probably have enough filter area for combustion air, as long as the filters are clean. Your methods are not up to codes though! Why not get the combustion air from outside and close the room off completely from the shop area? Also, as for sealing around the vent pipe it depends on the type of venting. I can not see your furnace from here, but single wall vent typically needs 6" if clearance to combustibles, double wall "B" vent needs 1". Combustibles are wood, sheetrock, wood paneling, plywood, etc. To seal a wall where the venting passes through the best way is to leave a hole large enough for the clearances required, then seal up the rest with sheet metal cut to fit around the pipe. I highly recommend getting a local HVAC tech to look things over for you. After all it is you home and families lives we are talking about here! Greg
Response:
Well, I was not aware that I could bring in combustion air, I’ve read that most furnaces now days have that though. What part am I doing that is not up to codes? I assumed closing the room off entirely, which is what I really want to do was a no no. I see on the side of my furnace a cutout for a air duct that goes in the combustion chamber, I assume this is where the air would enter. Is it typically blown in via a fan or just open duct to outside? Yes, I was well aware it might not be code, how this house even made it past an inspector in the first place is beyond me. I will call a HAVAC man before I put the door on.
– Hide quoted text — Show quoted text – . I’ve quite often seen gas furnaces and waters heaters in closed off rooms with no type of incoming air. I have too, it does not mean it is right though! You probably have enough filter area for combustion air, as long as the filters are clean. Your methods are not up to codes though! Why not get the combustion air from outside and close the room off completely from the shop area? Also, as for sealing around the vent pipe it depends on the type of venting. I can not see your furnace from here, but single wall vent typically needs 6" if clearance to combustibles, double wall "B" vent needs 1". Combustibles are wood, sheetrock, wood paneling, plywood, etc. To seal a wall where the venting passes through the best way is to leave a hole large enough for the clearances required, then seal up the rest with sheet metal cut to fit around the pipe. I highly recommend getting a local HVAC tech to look things over for you. After all it is you home and families lives we are talking about here! Greg
Response:
If you were to proceed as planned, I believe you would find that you would experience one of the following problems: 1. Furnace would either fail to start or shut down and lock out on the airflow sensor safety switch. 2. Flame rollout sensor would open circuit causing shutdown and requiring service call to replace. Also, Expanding foam could release toxic fumes when heated. You will need to supply additional air from outside. You do not need to "pump" air into the room. But you should run a 6" duct from the outside to the front of the furnace by the burner compartment. You cannot have a negative pressure in the room containing the furnace while the furnace is operating. Do NOT put expanding foam on the vent pipe. There should be no need to seal the vent pipe. As for the pipe being hot, the efficiency rating of the furnace determines the flue gas temperatures. For a non-condensing furnace, the flue gas temperature needs to be 350 deggrees + the combustion air temperature to prevent condensing in the flue pipe/chimney. Hope this is helpful to you. Former HVAC technician – Hide quoted text — Show quoted text – I have closed off my gas furnace and sealed all the cracks with expanding foam, door not on yet, and have four 16×25x1 air filters built in to the wall. When I do put the door on will I need to pump combustion air in or will the filters allow enough flow? Also the vent pipe from the furnace goes outside one of the walls, it seems to get very hot, what is safe to put on the outside of the pipe to seal things off? expanding foam? Thanks
Response:
Chill out? OK, Chip, whatever you say (this is me packing my tools, walking down your driveway shaking my head and getting in my pick-up truck to drive away) Best of luck Chip, and I do mean it. Rob
– Hide quoted text — Show quoted text – well, maybe I should have been more clear. I have built 2 walls 10 feet out on each side from the furnace. One of the walls contains 4 25×16x1 furnace filters, so one wall is half filters. The room is by no means closed off to air, Yes I did seal off the other joints except for the door which is not on yet. I have not altered how the furnace vents, I just want to seal around the vent pipe. This mainly to seal out dust, yes I have several dust collectors and filters but dust still gets in. I’ve quite often seen gas furnaces and waters heaters in closed off rooms with no type of incoming air. Let’s all chill out for the moment. I have closed off my gas furnace and sealed all the cracks with expanding foam, door not on yet, and have four 16×25x1 air filters built in to the wall. When I do put the door on will I need to pump combustion air in or will the filters allow enough flow? Also the vent pipe from the furnace goes outside one of the walls, it seems to get very hot, what is safe to put on the outside of the pipe to seal things off? expanding foam? Thanks First, you should not be doing what you are doing. The fact that you have done this much without proper knowledge could put your family at risk. This was not smart. Furnaces have vent requirements. Check the owners manual. Some must have 3-4 feet of free space in front or on the sides, others can be located pretty close to a wall. Each brand has its own requriements. As for make up air, it depends on the furnace and the efficiency. Mine is about 10 years old, 80+, and it gets make up air from the house. Choking off that air supply could cause all kinds of problems including failure to vent, which could kill everyone in the house potentially. Yes, there are safety features to prevent this, but I would rather do it right than rely on a feature. If you do not get a good vent, which could happen with a lack of make up air, the fumes stay in the house. At the least, get a carbon monoxide detector near the furnace RIGHT NOW. Some models use a direct vent system where the intake and exhaust come through one pipe. The inside pipe does one while the space around it does the other. In this case make up air is usually not needed.
Response:
Just because I don’t see it you’re way you’re gonna leave?, you must be a very stressed out man. Well, try not to road rage anyone on your way home.
– Hide quoted text — Show quoted text – Chill out? OK, Chip, whatever you say (this is me packing my tools, walking down your driveway shaking my head and getting in my pick-up truck to drive away) Best of luck Chip, and I do mean it. Rob well, maybe I should have been more clear. I have built 2 walls 10 feet out on each side from the furnace. One of the walls contains 4 25×16x1 furnace filters, so one wall is half filters. The room is by no means closed off to air, Yes I did seal off the other joints except for the door which is not on yet. I have not altered how the furnace vents, I just want to seal around the vent pipe. This mainly to seal out dust, yes I have several dust collectors and filters but dust still gets in. I’ve quite often seen gas furnaces and waters heaters in closed off rooms with no type of incoming air. Let’s all chill out for the moment. I have closed off my gas furnace and sealed all the cracks with expanding foam, door not on yet, and have four 16×25x1 air filters built in to the wall. When I do put the door on will I need to pump combustion air in or will the filters allow enough flow? Also the vent pipe from the furnace goes outside one of the walls, it seems to get very hot, what is safe to put on the outside of the pipe to seal things off? expanding foam? Thanks First, you should not be doing what you are doing. The fact that you have done this much without proper knowledge could put your family at risk. This was not smart. Furnaces have vent requirements. Check the owners manual. Some must have 3-4 feet of free space in front or on the sides, others can be located pretty close to a wall. Each brand has its own requriements. As for make up air, it depends on the furnace and the efficiency. Mine is about 10 years old, 80+, and it gets make up air from the house. Choking off that air supply could cause all kinds of problems including failure to vent, which could kill everyone in the house potentially. Yes, there are safety features to prevent this, but I would rather do it right than rely on a feature. If you do not get a good vent, which could happen with a lack of make up air, the fumes stay in the house. At the least, get a carbon monoxide detector near the furnace RIGHT NOW. Some models use a direct vent system where the intake and exhaust come through one pipe. The inside pipe does one while the space around it does the other. In this case make up air is usually not needed.
Response:
possible editing): I have closed off my gas furnace and sealed all the cracks with expanding foam, door not on yet, and have four 16×25x1 air filters built in to the wall. When I do put the door on will I need to pump combustion air in or will the filters allow enough flow? Also the vent pipe from the furnace goes outside one of the walls, it seems to get very hot, what is safe to put on the outside of the pipe to seal things off? expanding foam? Thanks
Ditto the others’ warnings, but perhaps more germane is that (at least my understanding is) the proper way to supply combustion air to a furnace is to bring it in from the outside. I don’t have a furnace, I have oil-fired boilers, but we ran 6" metal pipe to an outside wall so that combustion air is brought in from the outside so that we don’t exhaust warm house air up the chimney. I’d expect that to be the proper solution with a gas furnace as well. This also eliminates the potential for carbon monoxide concentrations when attic fans are run in the summer when the boilers are still supplying hot water. — Larry
Response:
Nope, not stressed at all actually. My business is (commercial) HVAC, I’m a woodworker,I recently finished a new shop that some consider to be pretty cool and have been known to install the odd residential HVAC system as well. I figure this, as well as a few other attributes allows me a bit of license to insert a cautionary statement when I feel one is necessary. With your original post, and even after your second post, I felt, and feel, that a cautionary note is erring to the wise. Should you choose to bypass my information means naught to me really. You’re a grown-up and can make your own decisions. Doesn’t matter to me one way or the other actually, life (for me) will go on just fine regardless of your decision. As for me "leaving"? I’ve seen enough folk to know that there’s those that wil heed, and those that won’t an it’s not for me to convince you one way or the other. If you don’t consider my words of value, then I’m simply not going to spend time trying to convince you…I have other things to do. so, I really do mean Good luck Chip, I hope it all works out. Road rage? Nope….life’s too short. Rob http://www.robswoodworking.com
– Hide quoted text — Show quoted text – Just because I don’t see it you’re way you’re gonna leave?, you must be a very stressed out man. Well, try not to road rage anyone on your way home. Chill out? OK, Chip, whatever you say (this is me packing my tools, walking down your driveway shaking my head and getting in my pick-up truck to drive away) Best of luck Chip, and I do mean it. Rob well, maybe I should have been more clear. I have built 2 walls 10 feet out on each side from the furnace. One of the walls contains 4 25×16x1 furnace filters, so one wall is half filters. The room is by no means closed off to air, Yes I did seal off the other joints except for the door which is not on yet. I have not altered how the furnace vents, I just want to seal around the vent pipe. This mainly to seal out dust, yes I have several dust collectors and filters but dust still gets in. I’ve quite often seen gas furnaces and waters heaters in closed off rooms with no type of incoming air. Let’s all chill out for the moment. I have closed off my gas furnace and sealed all the cracks with expanding foam, door not on yet, and have four 16×25x1 air filters built in to the wall. When I do put the door on will I need to pump combustion air in or will the filters allow enough flow? Also the vent pipe from the furnace goes outside one of the walls, it seems to get very hot, what is safe to put on the outside of the pipe to seal things off? expanding foam? Thanks First, you should not be doing what you are doing. The fact that you have done this much without proper knowledge could put your family at risk. This was not smart. Furnaces have vent requirements. Check the owners manual. Some must have 3-4 feet of free space in front or on the sides, others can be located pretty close to a wall. Each brand has its own requriements. As for make up air, it depends on the furnace and the efficiency. Mine is about 10 years old, 80+, and it gets make up air from the house. Choking off that air supply could cause all kinds of problems including failure to vent, which could kill everyone in the house potentially. Yes, there are safety features to prevent this, but I would rather do it right than rely on a feature. If you do not get a good vent, which could happen with a lack of make up air, the fumes stay in the house. At the least, get a carbon monoxide detector near the furnace RIGHT NOW. Some models use a direct vent system where the intake and exhaust come through one pipe. The inside pipe does one while the space around it does the other. In this case make up air is usually not needed.
Response:
Just because I don’t see it you’re way you’re gonna leave?, you must be a very stressed out man. Well, try not to road rage anyone on your way home.
You ask for advice, and as soon as someone (actually everyone who answered) tells you what a moron you are you say chill out. And nobody even used the term moron, we actually were very nice to explain that you could kill yourself and family. I used to work in a plumbing and heating supply house in Chicago. I remember clueless people coming in looking for parts they didn’t understand, telling me to just give them something that works. No matter how hard I tried to explain to them that it would cause a fire or explosion, they never seemed to care – saving a buck was more important than their safety. Then, one day, I started asking them for their address. Confused, they would ask why. I would reply that when their house exploded, the news would most likely be there to show it on TV, and I wanted to know if it was their house or some other idiots. That usually got them to listen. Why aren’t you?
Response:
Just had a chat with the furnace guy while he didi the anual maintenance on our burner. Asked about dust and basement shops, and he suggested that (if I put a shop in the basement) I get a little device that draws all the combustion air from outside. said it would be about $200 to $250, installed. Sounds like the simplest most effective way to deal with the whole problem…… –JD
– Hide quoted text — Show quoted text – If you were to proceed as planned, I believe you would find that you would experience one of the following problems: 1. Furnace would either fail to start or shut down and lock out on the airflow sensor safety switch. 2. Flame rollout sensor would open circuit causing shutdown and requiring service call to replace. Also, Expanding foam could release toxic fumes when heated. You will need to supply additional air from outside. You do not need to "pump" air into the room. But you should run a 6" duct from the outside to the front of the furnace by the burner compartment. You cannot have a negative pressure in the room containing the furnace while the furnace is operating. Do NOT put expanding foam on the vent pipe. There should be no need to seal the vent pipe. As for the pipe being hot, the efficiency rating of the furnace determines the flue gas temperatures. For a non-condensing furnace, the flue gas temperature needs to be 350 deggrees + the combustion air temperature to prevent condensing in the flue pipe/chimney. Hope this is helpful to you. Former HVAC technician
– Hide quoted text — Show quoted text – I have closed off my gas furnace and sealed all the cracks with expanding foam, door not on yet, and have four 16×25x1 air filters built in to the wall. When I do put the door on will I need to pump combustion air in or will the filters allow enough flow? Also the vent pipe from the furnace goes outside one of the walls, it seems to get very hot, what is safe to put on the outside of the pipe to seal things off? expanding foam? Thanks
Response:
Actually if your furnace room is sealed as you say, the easiest way to bring in combustion air is to simply pipe it into a 5 gallon bucket inside your furnace room. This prevents a negative pressure (i.e. suck in dust), and at the same time prevents drafts due to cold air intake. BTW the five gallon pail is simply there to prevent a thermal siphon where your furnace room would fill with sub zero air (if you live in the great white north). This is a common set up in northern Canada (I reside in Fort McMurray, about 300 miles north of Edmonton, Alberta, it was -25C Friday). Dave – Hide quoted text — Show quoted text – Just had a chat with the furnace guy while he didi the anual maintenance on our burner. Asked about dust and basement shops, and he suggested that (if I put a shop in the basement) I get a little device that draws all the combustion air from outside. said it would be about $200 to $250, installed. Sounds like the simplest most effective way to deal with the whole problem…… –JD If you were to proceed as planned, I believe you would find that you would experience one of the following problems: 1. Furnace would either fail to start or shut down and lock out on the airflow sensor safety switch. 2. Flame rollout sensor would open circuit causing shutdown and requiring service call to replace. Also, Expanding foam could release toxic fumes when heated. You will need to supply additional air from outside. You do not need to "pump" air into the room. But you should run a 6" duct from the outside to the front of the furnace by the burner compartment. You cannot have a negative pressure in the room containing the furnace while the furnace is operating. Do NOT put expanding foam on the vent pipe. There should be no need to seal the vent pipe. As for the pipe being hot, the efficiency rating of the furnace determines the flue gas temperatures. For a non-condensing furnace, the flue gas temperature needs to be 350 deggrees + the combustion air temperature to prevent condensing in the flue pipe/chimney. Hope this is helpful to you. Former HVAC technician I have closed off my gas furnace and sealed all the cracks with expanding foam, door not on yet, and have four 16×25x1 air filters built in to the wall. When I do put the door on will I need to pump combustion air in or will the filters allow enough flow? Also the vent pipe from the furnace goes outside one of the walls, it seems to get very hot, what is safe to put on the outside of the pipe to seal things off? expanding foam? Thanks
dave.kozlowski.vcf
< 1K Download
Response:
Alberta, it was -25C Friday
Only 300 miles north of Edmonton? Do you know Phil and Audrey?
Response: